Typical Applications
Intelligent building
Commercial HVAC
Technical Data
Input and output
|
Operating voltage |
24V DC ± 20% |
|
Current output |
4 ... 20mA RL < 500 Ohm |
|
Power consumption |
< 20mA (current or voltage output) |
|
Voltage output |
0 ... 10V |
|
|
|
|
|
Channel precision: ±0.2%FS |
|
|
< 6mA (digital output) |
|
Digital output |
RS485 (Modbus RTU) |
Measurement Parameter
|
Relative humidity |
|
|
Temperature |
|
|
Measurement range |
0 ... 95%RH |
|
Measurement range |
?40 … +80°C |
|
Measurement precision |
±3%RH (20 … 80%RH & 25℃) |
|
Measurement precision |
±0.5°C (25℃) |
|
τ63 response time |
15s |
|
- - |
- - |
|
Sensor |
Digital temperature and humidity sensor |
|
- - |
- - |
|
|
|
|
||
The above precisions are comprehensive precisions, including repeatability, linearity and hysteresis of the measurement, and can be traced to the CNAS standard.
Technical Specification
|
Wiring connection |
The maximum cable diameter of the terminal is 1.5mm2 |
|
Operating temperature |
Without display: -40 ... 80℃ |
|
Cable connector |
M16*1.5 gland connector (threading diameter 4.5~10mm) |
|
|
With display: -20 ... 60℃ |
|
Shell material |
PC (flame-retardant grade UL94-V0)
|
|
Storage temperature |
-20 ... 60℃ |
|
Probe protection |
Plastic film filter |
|
Electromagnetic compatibility |
EN61326-1 EN61326-2-3 |
|
Protection grade |
IP65 |
|
|
|